LogicPro Users Guide Chapter 12: Function Blocks
Doc.# 28002-00 Rev 3.00 Watlow Anafaze 195
PPC-2030 Encoder In Analog Out Addressing Example
To create a variable named CountIn_3 that reads the count on the
third input on a PPC-2030 module with its rotary address switch set
to 14, set the options in the Add Program/Resource Variable
dialog box as illustrated below.
Digital_IO_2040
The Digital_IO_2040 driver supports the inputs and outputs on the
PPC-2040 Digital IO Module.
To associate a variable with a digital I/O point:
1. Open the Add Program/Resource Variable dialog box.
2. Enter a unique variable Name.
3. Select BOOL from the Type list.
4. Select Input or Output by clicking the corresponding check
box.
5. Select Digital_IO_2040 from the IO Driver list.
6. Enter the IO Physical Address. The address is:
X.0.Z X is the module address (21-26)
Z is the module I/O number (1-32).
7. Click [OK].