4-42
|----------------------------------------------------|
¦ NOTE: When leaving ramp and soak mode the loop is ¦
¦ placed in MANUAL mode and the output is set to 0. ¦
|----------------------------------------------------|
Example problems and solutions
PROBLEM: Length of a segment is unknown and depends solely on a trigger input for
conclusion.
SOLUTION: Enter the smallest interval possible, define a trigger for the subsequent
segment. The first condition for conclusion will be satisfied when the interval period
elapses but the next segment will not commence until the trigger occurs.
PROBLEM: Separate profiles have different setpoints, triggers and events but the basic
timing pattern is identical.
SOLUTION: Edit the common variables on one profile (perhaps on an unused profile),
copy that profile into each individual ramp and soak profile as a basic template and edit
specific details from there.