118 8LS Users Guide
Appendix B: 8LS-CP
Burn Off Time Period
This menu is displayed if the start mode is set to either Input or Time.
Use it to edit the time period of the burn off. This is the time that the
burn off air flow output will be set On to allow air flow to the probe
burn off port.
Selectable Range: 1-45.
Maximum Allowable Probe Temperature
This menu is displayed if the start mode is set to either Input or Time.
Use it to edit the maximum allowable probe temperature during the burn
off procedure. When this temperature exceeds the burn off air flow,
digital output is set Off until the probe temperature is 100
º
F below the
Maximum Allowable Probe Temperature Setpoint. When the output is
Off, the air flow to the probe should stop, allowing the probe to cool
down.
Selectable Range: 1900
º
F or 2100
º
F (1038
º
C or 1149
º
C).
Burn Off Air Flow Output Number
This menu is displayed if the start mode is set to either Input or Time.
Use it to edit the digital output number that controls the burn off air
flow. Setting the number to 0 means the air flow digital output will not
be activated.
Selectable Range: 1-30 or 0.
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
2BO TIME
MINS? 5
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT STATUS OUTPUT%
2BO TEMP
MAX? 1900
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
2BO AIR
OUTPT? 0