Installation
CAS Users Guide 31
Recommended Wire Gauges
Watlow Anafaze recommends the following maximum distances and
wire gauges:
You may wish to use a shield, depending on your noise environment and
grounding problems. The above cables are shielded.
NOTE
These recommendations are conservative, to ensure that the CAS
will operate reliably. Expect satisfactory performance even if you
must deviate slightly from a design specification.
Distance Wire Gauge
Recommended
Cable
4000 ft. 24 AWG Belden #9729
Belden #9842
6000 ft. 22 AWG Belden #9184