Calibrating Watlow Process Controls(Applies to Series 981, 982, 983, 984, 986, 987, 988, 989)Calibration ManualWatlow Controls, 1241 Bundy Blvd., P.O.
10 WATLOW Series 988 Calibration ManualRTDRTD Input ProcedureEquipment Required•1K precision decade box with 0.01 resolutionSetup and Calibration1.
WATLOW Series 988 Calibration Manual 11mA Process InputmA Process Input Procedure0 to 20mA and 4 to 20mA unitsEquipment Required• Precision current so
12 WATLOW Series 988 Calibration ManualVDC Process Input Procedure0 to 5VDC and 0 to 10VDC unitsEquipment Required• Precision Voltage source 0-10 volt
WATLOW Series 988 Calibration Manual 13mVDC Process InputmVDC Process Input Procedure0 to 50mVDC and 0 to 100mVDC unitsEquipment Required• Precision m
14 WATLOW Series 988 Calibration ManualSlidewire/CurrentSlidewire Feedback Input ProcedureEquipment Required•1K precision decade box with 0.01 resol
WATLOW Series 988 Calibration Manual 15mA Process OutputmA Process Output 1 & 2 ProcedureEquipment Required• 4 1/2 digit digital multimeterSetup a
16 WATLOW Series 988 Calibration ManualVDC Process OutputVDC Process Output 1 & 2 CalibrationEquipment Required• 4 1/2 digit Digital MultimeterSet
WATLOW Series 988 Calibration Manual 17Retransmit mA Retransmit Output 3 ProcedureEquipment Required• 4 1/2 digit Digital MultimeterSetup and Calibrat
18 WATLOW Series 988 Calibration Manual
Watlow Process Controls Calibration ManualWatlow Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona, MN 55987-5580, Phone: 507/454-5300, Fax: 507/452-4
2 WATLOW Series 988 Calibration ManualContentsPage DescriptionCalibrating Your Watlow Process Control3 The Factory (Fcty) Menus3 Entering the Fcty Pro
WATLOW Series 988 Calibration Manual 3Menus/PromptsCalibrating Your Watlow Process ControlThis manual is a supplement to the Series 981/982 and 988/98
TLWWAPROCESSL1 L2 L3 L4DEV% OUTDISPLAYSERIES 988MODEAUTOMAN4 WATLOW Series 988 Calibration ManualDiagnosticsDiagnostics MenuThe Diagnostics menu (diAg
WATLOW Series 988 Calibration Manual 5DiagnosticsWhen contacting the factory for technical assistance, make sure you have the informa-tion documented
6 WATLOW Series 988 Calibration ManualCAL MenuCalibration MenuEnter the Factory menu again by pressing the Up and Down keys simultaneouslyfor three se
WATLOW Series 988 Calibration Manual 7rSt/dFL PromptsCalibration Restore PromptIf you make a mistake while calibrating your control, the rSt prompt ne
Low Gain Thermocouple Input ProcedureFor all thermocouple inputs excluding Type R, S and BEquipment Required• Type J reference compensator with refere
WATLOW Series 988 Calibration Manual 9High Gain T/CHigh Gain Thermocouple Input ProcedureType R, S and B onlyEquipment Required• Type J reference comp