Watlow CLS200, MLS300 and CAS200 Manual do Utilizador Página 66

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 92
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 65
60 Communications Specification
Chapter 3: Controller Parameter Descriptions
Range: 0 to 255.
Default: 5.
Startup Alarm Delay (40)
This parameter designates a delay time for process and deviation alarms
on power-up. The controller does not report process and deviation
alarms for the specified number of minutes after the controller powers
up.
The startup alarm delay is a global alarm parameter; it applies to all
process and deviation alarms for every loop.
The startup alarm delay does not apply to failed-sensor alarms and AIM
failure alarms.
Range: 0 to 255 minutes.
Default: 0.
High Process Alarm Output Number (41)
This parameter assigns the output number to which the high process
alarm output is directed.
Range: 0 to 34.
Default: 0 (no high process alarm output).
Low Process Alarm Output Number (42)
This parameter assigns the output number to which the low process
alarm output is directed.
Range: 0 to 34.
Default: 0 (no low process alarm output).
High Deviation Alarm Output Number (43)
This parameter assigns the output number to which the high deviation
alarm output is directed.
Range: 0 to 34.
Default: 0 (no high deviation alarm output).
Low Deviation Alarm Output Number (44)
This parameter assigns the digital output number to which the low
deviation alarm output is directed.
Range: 0 to 34.
Vista de página 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 91 92

Comentários a estes Manuais

Sem comentários