Watlow Control Console ■ 5
Figure 3 — Control Console without a limit.
2. Heater Connections
The heater output(s) utilizes either AMP Mate-’n’-
Lok® connector(s) or twist-and-lock connector(s).
The mating connector and terminals are provided.
To ensure proper crimping of the AMP Mate-’n’-Lok®
terminals, the proper equipment should be used.
AMP recommends using part number 90300-2 for
terminal crimping and part number 458994-2 for
extraction of the terminals from the connector.
Please consult the TYCO-AMP Corporation at 1-800-
468-2023 for further information.
3. Thermocouple Connections
Using a small screwdriver, remove the two screws
holding the cover of the male miniature thermocou-
ple connector(s). Loosen, but do not remove the +
and - terminal screws. The connector(s) can accom-
modate wire sizes up to 20-gauge, stranded wire.
Insert the red wire from the thermocouple to the (-)
terminal of the connector(s). Do not wrap the wire
around the terminal. Repeat the step for the positive
thermocouple lead.
4. Communication Connections
EIA-232 Communications
• Female DB9 connector mounted in box
• Pin 2: receive
• Pin 3: transmit
• Pin 5: common
EIA-485 Communications
• Female DB9 connector mounted in box
• Pin 2: T-/R-(A)
• Pin 3: T+/R+(B)
• Pin 5: common
* To ensure proper crimping of the DB9 terminal,
the proper equipment should be used. AMP recom-
mends using part number 58448-2.
5. Start Up
For start up and function of the temperature con-
troller, please refer to the user's manual for the
respective temperature controller that is included
with the Console.
Comentários a estes Manuais