Watlow EZ-ZONE
®
RML Module 45 Chapter 4 Setup Page
RM Limit Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output (1
to 8)
Direction
Set this function to operate
as an input or output.
[OtPt] Output (68)
[``in] Input Voltage (193)
[iCon] Input Dry Contact
(44)
Output 1850
[offset 30]
0x6A
(106)
1 to 8
1
82 6001 uint
RWES
[`dir]
[ dir]
Digital Input (9)
Direction
Set the input type.
[``in] Input Voltage (193)
[iCon] Input Dry Contact
(44)
Dry Con-
tact
2090
[offset 30]
0x6A
(106)
9
1
82 6001 uint
RWES
[``Fn]
[ Fn]
Digital Output (1 to 6)
Function
Select what function will
drive this output.
[`oFF] Off (62)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[`FUn] Function Key (1001)
[`lnr] Linearization (238)
[`LgC] Logic (239)
[mat] Math (240)
[tMr] Timer (244)
[`uAr] Variable (245)
[m;li] Module Limit (1696)
[LiM] Limit (126)
1858
[offset 30]
0x 6A
(106)
1 to 6
5
83 6005 uint
RWES
[``Fi]
[ Fi]
Digital Output (1 to 8)
Function Instance
Set the instance of the
function selected above.
1 to 24 1 1860
[offset 30]
0x6A
(106)
1 to 8
6
84 6006 uint
RWES
[`S2;A]
[ SZ.A]
Digital Output (1 to 8)
Source Zone A
Set the zone of the function
selected above.
0 to 16 0 1872
[offset 30]
0x6A
(106)
1 to 8
0xC (12)
- - - - 6012 uint
RWES
[`o;Ct]
[ o.Ct]
Digital Output (1 to 8)
Control
Set the output control type.
This parameter is only
used with PID control, but
can be set anytime.
[`Ftb] Fixed Time Base (34)
[`utb] Variable Time Base
(103)
Fixed
Time
Base
1852
[offset 30]
0x6A
(106)
1 to 8
2
85 6002 uint
RWES
[`o;tb]
[ o.tb]
Digital Output (1 to 8)
Time Base
Set the time base for fixed-
time-base control.
[ 0.1 for Fast and Bi-Direc-
tional outputs, 5.0 for Slow
outputs] to 60
1854
[offset 30]
0x6A
(106)
1 to 8
3
86 6003 float
RWES
[`o;Lo]
[ o.Lo]
Digital Output (1 to 8)
Low Power Scale
The power output will nev-
er be less than the value
specified and will represent
the value at which output
scaling begins.
0.0 to 100.0 0.0 1866
[offset 30]
0x6A
(106)
1 to 8
9
87 6009 float
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set