Parameters
5.12 Watlow MicroDIN =Read Only; =Read/Write; =Turn On/Off
ON
Operation Group continued
User Set Point
• Change or monitor the control set point.
• Read/write
• Modbus: 300
Range
Range Low to Range High (Input Group)
Default
75°F, 24°C
Active
if Operation Mode (Operation Group) is set to auto
Affected by
Changing Sensor Type (Input Group) determines range of setting
and default
Changing Input Type (Input Group) determines range of setting
and default
Changing Range Low (Input Group) determines range of setting
and default
Changing Range High (Input Group) determines range of setting
and default
Changing C or F (System Group) determines range of setting
and default
Manual Output Power
• Set the control output power manually.
• Read/write
• Modbus: 310
Range
0.0 to 100.0: heat mode
-100.0 to 0.0: cool mode
Default
0.0
Active
if Operation Mode (Operation Group) is set to manual or
switches to manual due to error
Affected by
Changing Operation Mode (Operation Group) to manual or
manual due to error
Changing Control Output Function (Alarm Output Group)
determines range of setting