Watlow NAFEM Gateway Manual do Utilizador Página 41

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 51
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 40
41
Gateway Serial Device Entry
Select Configuration, Gateway, Serial Device Entry, and Object Instance 1 to access this page.
Configure a serial device entry for each device. A maximum of 8 devices can be configured.
Enter a Name for reference. Set the Assignment Port to 1.
Engaged must be set to Engage to have the device active.
Enter the Address of the Modbus device. The range is 1 to 247.
Set Port Delay, Health Check Rate and ID Check Rate to 0.
Write and Read Count indicates the number of attempted write and read instructions to this device.
The Write Error and Read Error Count are the number of failed attempts at writing and reading to this
device. The CRC Error Count is the number of packets returned with corrupted data within the
packet.
Note: Click Submit to save changes. Reset will return these settings to the previous values if you have
not pressed the Submit button.
Vista de página 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 50 51

Comentários a estes Manuais

Sem comentários