Watlow Series 101 Manual do Utilizador Página 3

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 6
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 2
Watlow Series 101 User’s Manual 3
Use the correct thermocouple type matching the model
number on the unit sticker. See the underside of the
unit.
Use the proper thermocouple polarity. Red is negative.
Insulate the thermocouple mounting from the mounting
surface to prevent heat migration input errors.
Thermocouple leads should be twisted pair wire and
routed separately from any other lines.
In electrically noisy environments (heavy switching of
contactor, motors, solenoids, etc.) use shielded thermo-
couple lead wire with the shield connected at the sensor
end only.
All wiring and fusing must conform to the National
Electric Code (NEC) NFPA70 and any other locally
applicable codes.
Fuse the independent load voltage on the L1 (hot) side
and connect it to the common (COM) side of the relay.
120VÅ 101 _ - 1 _ _ _ - 0000
230VÅ 101 _ - 2 _ _ _ - 0000
24VÅ 101 _ - 3 _ _ _ - 0000
NOTE: The line voltage is specified by your model number.
Figure 3a — Power wiring.
Ó
WARNING: To avoid potential electric shock, use National
Electrical Code safety practices when wiring and connecting this
unit to a power source and to electrical sensors or peripheral
devices.
All wiring and fusing must conform to the National Electric Code
and to any locally applicable codes.
Ó
WARNING: Applying incorrect voltage may result in irreversible
damage to the control.
NOTE: We strongly recommend that all control loops use an
approved temperature limit control for over or under temperature
limit protection. Failure to install temperature limit control pro-
tection where a potential hazard exists could result in damage to
equipment and property and injury to personnel.
Figure 3b — Thermocouple wiring.
NOTE: When an external device with a non-isolated circuit com-
mon is connected to the dc output, you must use an isolated or
ungrounded thermocouple.
Electromechanical Relay, Form C with suppression 3A
101A - _ _ _ _ - 0000
Solid State Relay, Form A, 0.5A without suppression
101B - _ _ _ _ - 0000
Figure 3c — Mechanical and solid-state relay wiring.
Switched DC
10 1C - _ _ _ _ - 0000
Figure 3d — Switched dc wiring.
dc+
dc-
External
Device
dc-
dc+
18V
Î
(dc)+
dc-
Internal Circuitry
Fuse
L1
L2
External
Device
Output Wiring
+
tc
-
tc
Input Wiring
Fuse
L1
L2
L1
L2
Power Wiring
Wiring Guidelines
Vista de página 2
1 2 3 4 5 6

Comentários a estes Manuais

Sem comentários