Table 8
-
SYSTEM Prompts and
Description.
Make photocopies,
keeD
original
clean:
CLR
ALARM
Displays
the
current
alarm.
1-2
RETURN
Press
the
ENTER
key to return to
SYSTEM prompt
Press the MODE key to return to the
SP
prompt.
;f+Rpj
.:.:.:.:.
g:“..:“.’
.
.
.
.
:,:.:.:.:
:
:
.,
.
.
.
~
,.
.
.
.
.:
::
.: .
l?IIzIl
,g?#@~~:
:..
_1.:.,.:.
.
.
.
.
.
.
.
.
.
.
.
.
.
.,.:...::
..,.
.
.
.,.;.y..
RETURN
1
From any
RETURN,
you can go
back to SYSTEM prompt.
One of three main
level operating menus. From the SYSTEM menu, you can generate a
non-
ramp set point (fixed), manipulate Events 1 and 2 ON or OFF, clear system errors, and clear
latching alarms.
.
Represents the current set point.
Range:
RAL
and RAH Default:
73°F
This auxiliary output can be an
alarm
or event.
Events may be turned ON or OFF in the
HOLD
mode.
EV1
will only appear when
AUX1
=
EV,
under the SPCLFUNC menu.
Range: OFF or ON
Default: OFF
This auxiliary output can be an alarm or event.
Events may be turned ON or OFF in the
HOLD mode.
EV2 will only appear when AUX2
=
EV,
under the SPCLFUNC menu.
Range: OFF or ON
Default: OFF
ER1
is considered a fatal error; your system will shut down. When the Serles 920 shuts down,
all outputs are turned off, and your program stops running. When an error occurs,
ER1
00XX
alternately flashes with the SYSTEM parameter. When in either the RUN or HOLD mode,
press the ENTER key to stop
ER1
from flashing for
5
minutes. This will not clear the
error
condition.
To clear an error, ENTER the SYSTEM mode, and scroll to the
ER1
parameter.
Press ENTER; this clears the error unless it is a
re-occuring
error and has not been resolved.
Range: 0
-
50
ER2
is
considered
non-fatal. if you are in the RUN mode, your program continues running
unless it is a
program
error.
ER2
00XX
appears, and flashes alternately along with the
parameter you are presently on. When in either the RUN or HOLD mode, pressing the
ENTER key
steps
ER2
from flashing for
5
minutes. This will not clear the error condition.
Clear an
ER2
by pressing the ENTER key while in the RUN mode, or return to the
ER2
parameter under the SYSTEM mode. Press ENTER. If the error persists, refer to the Error
Code
list at the
end of the manual to clear.
Range: 0 -
50
Alarms 1
and
2 are considered non-fatal. If you are in the RUN mode, your program will
continue to run.
ALMX XX
appears and flashes alternately with the parameter you are
presently
on. When in either the RUN or HOLD mode, press the ENTER key to stop
ER1
from flashing for 5 minutes. This will not clear the alarm condition. ENTER the CLR
ALARM
parameter to clear a latching alarm. A non-latching alarm clears itself once it fails within the
alarm
limits.
Range:
1
- 2
How To
Program
the Series 920, Chapter 6
WATLOW
Series 920 User’s Manual
41