Controller
Microprocessor based, limit controller.
Nominal switching hysteresis, typically 1.7°C (3°F)
High or low limit, factory selectable.
Latching output requires manual reset upon over
or under temperature condition.
Manual or automatic reset on power loss, factory
selectable.
Internal front panel or external customer supplied
momentary reset switch.
Input filter time: 1 second.
Operator Interface (model dependent)
Four digit , 7 segment LED displays, .28" high.
°F or °C indicator LED.
ALARM indicator LED.
Continuous turn, velocity sensitive rotary encoder
for limit set point adjustment.
Front panel SET/RESET key on variable set point
models.
No operator interface on fixed set point models.
Standard Conditions For Specifications
Rated line voltage, 50 to 60Hz, 0 to 90% RH non-
condensing, 15-minute warm-up.
Calibration ambient range: 25°C (77°F) ±3°C
Sensor Input
Thermocouple
Grounded or ungrounded.
Type E, J, K, T thermocouple types.
>10 MΩ input impedance.
250 nV input referenced error per 1 Ω source resis-
tance.
RTD
2-wire platinum, 100 Ω.
DIN curve (.00385 curve).
125 μA nominal RTD excitation current.
Input Accuracy Span Range
Thermocouple Input
Type E -200 to 800°C or -328 to 1,470°F
Type J: 0 to 750°C or 32 to 1,382°F
Type K: -200 to 1,250°C or -328 to 2,282°F
Type T: -200 to 350°C or -328 to 662°F
RTD (DIN): -200 to 800°C or -328 to 1,472°F
Calibration accuracy: ±1% of input accuracy span,
±1° at standard conditions and actual calibration
ambient.
Exception: Type T, ±2.4% of input accuracy span
for -200 to 0°C (-328 to 32°F)
Temperature stability: ±0.3 degree per degree
change in ambient.
RTD Input
Calibration accuracy: ±1% of input accuracy span
±1° at standard conditions and actual calibration
ambient.
Temperature stability: ±0.2 degree per degree
change in ambient
Allowable Operating Ranges
Type E -200 to 800°C or -328 to 1,470°F
Type J: -210 to 1,038°C or -346 to 1,900°F
Type K: -270 to 1,370°C or -454 to 2,500°F
Type T: -270 to 400°C or -454 to 750°F
RTD (DIN): -200 to 800°C or -328 to 1,472°F
External Reset Switch
Momentary, dry contact closure. See wiring section.
Output Types
Electromechanical Relay, Form C
Minimum load current: 100 mA.
8 A @ 240VÅ (ac) or 30VÎ (dc) maximum, resistive.
250 VA pilot duty, 120/240VÅ (ac) maximum, in-
ductive.
Use RC suppression for inductive loads.
Electrical life 100,000 cycles at rated current.
Agency Approvals
Series LF (potted version only)
UL 991 recognized temperature limit for food ser-
vice industry.
RoHS Directive (2002-95-EC)
Series LV and Series LF (including potted version)
UL 873 recognized temperature regulator. File
#E43684.
UL 197 reviewed for use in food service appliances.
ANSI Z21.23 Gas appliance thermostat approval.
CSA C22.2#24 approved temperature control. File
#30586.
FM Class 3545 temperature limit switches. File
#3017239.
NEMA 4X/IP65 on panel-mount versions with tac-
tile keys for set point adjustment.
W.E.E.E.; CE - see Declaration of Conformity.
RoHS Directive (2002-95-EC)
Terminals
6.4 mm (0.25 in) quick connect, push-on termi-
nals. See order options. Refer to Wiring section for
crimp-on terminal recommendations.
Removable screw clamp style terminal blocks. See
order options.
Wire gauge 0.1 to 4 mm
2
(30 to 12 AWG). Strip
length, 8 mm (0.30 in).
Torque
:
0.8 Nm (7 in-lb) maximum.
Speci cations