Silver Series Operator Interface Terminals
EZware-5000 Programming Manual
Operator Interface Terminals
1241 Bundy Boulevard, Winona, Minnesota USA 55987
Phone: +1 (800) 492-8569, Fax: +1 (507) 452-4507 http://www.watlow.com
0600-0068-0000 Rev. C ©2014 Watlow and Maple Systems. All rights reserved.
March 2014
Vista de página 0
1 2 3 4 5 6 ... 203 204

Resumo do Conteúdo

Página 1 - Operator Interface Terminals

Silver Series Operator Interface Terminals EZware-5000 Programming Manual Operator Interface Terminals

Página 2 - APPLICATIONS ASSISTANCE

2 EZware5000 Series Programming Manual Icon Meaning  Identifies a procedure.  Indicates a reference to additional information.  Indicates

Página 3

92 EZware5000 Series Programming Manual 6. Disable buzzer: When checked, the HMI will not sound the buzzer (beep) when the screen is touched. Loca

Página 4

Using EZware-5000 93 To configure Security tab settings: The Security tab is used to set up a table of users, user levels (access classes), and p

Página 5 - Table of Contents

94 EZware5000 Series Programming Manual The object can be configured to handle insufficient security in one of two ways: • The object can be hidd

Página 6

Using EZware-5000 95 LW9500, LW9501 New password, user 1 32-bit unsigned Loaded into security system when LB9061 is set momentarily LW9502, LW9503

Página 7

96 EZware5000 Series Programming Manual To configure Font tab settings: Determines the font for non-ASCII strings. To add a Windows TrueType font

Página 8

Using EZware-5000 97 To configure the Extended Memory tab settings: The Extended Memory tab is used to configure the extended memory for saving d

Página 9 - Chapter 1 – Introduction

98 EZware5000 Series Programming Manual To configure Printer/Backup Server tab settings: 1. Check the Use Remote Printer/Backup Server checkbox

Página 10 - What You Need

Using EZware-5000 99 Automatically Reboot HMI EasyBuilder can automatically reboot the HMI after download. To enable automatic reboot of HMI after

Página 11 - OIT/HMI Basics

100 EZware5000 Series Programming Manual 3. By default, the converted file is automatically placed into the same directory. To modify the name of

Página 12 - Windows

Using EZware-5000 101 7. Click the Exit button to go back to the main screen of EasyBuilder-5000. Open the converted file as you would normally o

Página 13 - List of Features

Introduction 3 OIT/HMI Basics Operator Interface Terminals (OITs) and Human Machine Interfaces (HMIs) provide much more versatility than traditiona

Página 14

102 EZware5000 Series Programming Manual Please Note: These files are captured by the HMI and stored in internal HMI memory, an attached SD card, o

Página 15 - Chapter 2 – HMI Local Setup

Using EZware-5000 103 2. Display Milliseconds: This option determines how the time value for each data record is displayed. In this window you hav

Página 16 - Changing the System Settings

104 EZware5000 Series Programming Manual we want to use these same changes on other files, click the Save Setting… button to save the changes as a

Página 17

Using EZware-5000 105 Converting Multiple Files EasyConverter also has a feature that allows you to select multiple Data/Event Log files and save

Página 18

106 EZware5000 Series Programming Manual EasyPrinter The Easy Printer button allows monitoring of the print server through Project Manager. The Eas

Página 19

Using EZware-5000 107 Options Menu > Settings The Settings window is used to configure the operation of EasyPrinter. General Port Number of the

Página 20

108 EZware5000 Series Programming Manual To create a new Recipe/Extended Memory file: From the Project Manager application, click Recipe/Extended

Página 21 - Viewing System Information

Using EZware-5000 109 integer format or BCD?). Therefore, the data format is used to define how each data element is formatted (ie., Signed vs Unsi

Página 22

110 EZware5000 Series Programming Manual 6. Select your data format: Use to select or create a data format template that can be used for other rec

Página 23

Using EZware-5000 111 b. Save file as *.emi for extended memory files.  You must use file names which correspond to the ten extended memory area

Página 24

4 EZware5000 Series Programming Manual Graphics Object A Graphics Object is any text, icon, or picture that can be displayed on the HMI. Graphics o

Página 25

112 EZware5000 Series Programming Manual EasyAddressViewer Starts the Easy Address Viewer application for viewing the device types and memory range

Página 26 - 1010-1007, Rev. 10

Using EZware-5000 113 Off-line Simulation Opens a compiled project (*.xob) in off-line simulator mode. Pass-through mode The pass-through mode allo

Página 27

114 EZware5000 Series Programming Manual 5. Destination COM Port (HMI -> PLC): Set COM settings for the HMI COM port that will be connected to

Página 28

Using EZware-5000 115 5. Click Uninstall to uninstall the virtual COM port driver on the PC.  The HMI must be powered and connected to the PC or

Página 29

116 EZware5000 Series Programming Manual Chapter 7 – Creating Windows This section shows how to create and use windows using EasyBuilder. Window

Página 30

Creating Windows 117 3. The Open Window dialog box closes and the opened window is displayed in the EasyBuilder work area. The Open Window dialog

Página 31

118 EZware5000 Series Programming Manual #55:ASCII Small – A style of an ASCII keypad. #60:ASCII Upper M – A style of an ASCII keypad. #61:ASCII Lo

Página 32

Creating Windows 119 4. Modify the window parameters, then press OK. The Open Window dialog box reappears. 5. If you wish to open the window you

Página 33 - HMI5000 Series

120 EZware5000 Series Programming Manual Assigning Size of Window You can vary the size of a new window to create full screen or popup windows. Pop

Página 34 - Troubleshooting

Creating Windows 121 Assigning Underlay Windows An Underlay Window is a Base Window that is displayed at the same time as the Base Window that call

Página 35 - To create Window 11:

Introduction 5 List of Features The next chapter will guide you through the creation of your first project. Before you proceed, you may wish to rea

Página 36

122 EZware5000 Series Programming Manual • Underlay windows are always positioned from the top left corner of the screen. Any position settings yo

Página 37 - To create a Function Key:

Creating Windows 123 Deleting a Window Before any window can be deleted from a project, the window must be closed. To close a window, see the secti

Página 38

124 EZware5000 Series Programming Manual 5. Select the Label tab and check Use label and create a label for the function key. 6. Click OK to retu

Página 39

Creating Windows 125 1. From the Objects menu, select PLC Control. The PLC Control Object dialog box appears. 2. Click New... The PLC Control d

Página 40 - To create a Bargraph:

126 EZware5000 Series Programming Manual 7. You will see a new entry that lists the PLC address that is monitored by the HMI. The PLC must only en

Página 41

Creating Windows 127 3. Click the Setting… button in the Read address section and select the PLC address according to Device type selected from th

Página 42

128 EZware5000 Series Programming Manual Tips and Suggestions Having trouble deciding which method to use to display a base window? Here are some

Página 43 - To create a Set Word:

Creating Windows 129 4. Place the function key object onto the popup window.  Placing a Close window function key onto a full-size base screen wi

Página 44

130 EZware5000 Series Programming Manual 3. As you can see, some of the parameters for a common window are disabled and cannot be changed. Window

Página 45

Creating Windows 131 Common Window When Above base window is set, the result is: When Below base window is set, the result is: To set the Above

Página 46

6 EZware5000 Series Programming Manual Video In Input and play video on the HMI from an external source (X-models only). Bar Graph Creates a bar

Página 47 - To create a Bit Lamp:

132 EZware5000 Series Programming Manual Therefore, a Set Word Object on a base window will cover a Rectangle Object on a common window that occupi

Página 48

Creating Windows 133 Default Common Window #4 Alternate Common Window #30 Initial Window #10 1010-1007, Rev. 10

Página 49

134 EZware5000 Series Programming Manual When the HMI initializes, it displays the startup screen (Window #10) and the default common window. To c

Página 50 - To create a Set Bit:

Creating Windows 135 To open a fast selection window: 1. From the Window menu, select Open Window. The Open Window dialog box appears. 2. Highl

Página 51

136 EZware5000 Series Programming Manual Using the Fast Selection Button The fast selection button is used to display the Fast Selection window. P

Página 52 - Saving your first project

Creating Windows 137 4. Click Settings... Click the Use shape checkbox, and then click the Shape Library… button. 5. Select a shape for your fast

Página 53 - Compiling your first project

138 EZware5000 Series Programming Manual The amount of available memory is indicated by the following Reserved Local Words: LW9072 HMI free space

Página 54

Creating and Using Databases and Languages 139 Chapter 8 – Creating and Using Databases and Languages EasyBuilder includes the ability to create a

Página 55

140 EZware5000 Series Programming Manual 3. Enter the new Tag name. Tag names may be up to 100 characters, any character. 4. Select the PLC name:

Página 56

Creating and Using Databases and Languages 141 To export the tag library to a .csv file or .xls file: 1. Click Export CSV or Export EXCEL. The Op

Página 57 - Chapter 5 – Simulator Mode

HMI Local Setup 7 Chapter 2 – HMI Local Setup Factory Configuration Each HMI arrives from the factory with a demo project file that illustrates som

Página 58

142 EZware5000 Series Programming Manual Creating the Label Library The Label library is a database of text Labels, for use with objects utilizing

Página 59 - To use EasySimulator

Creating and Using Databases and Languages 143 5. The new label is still selected. Click the Settings… button to display the Label Tag Content di

Página 60 - The Project Manager

144 EZware5000 Series Programming Manual To set a different font for each language: 1. From the Library menu, click Label..., or click the Label

Página 61 - Editor Settings

Creating and Using Databases and Languages 145 To export the label library: 1. Click Export EXCEL File… The Open dialog box appears. 2. Enter th

Página 62

146 EZware5000 Series Programming Manual 1. Text Labels in any of up to eight languages can be displayed, as configured in the Label Library. In L

Página 63

Using and Creating Keypads 147 Chapter 9 – Using and Creating Keypads The HMI operator must have a keypad available to enter new data when using t

Página 64

148 EZware5000 Series Programming Manual 2. Use the Description: box to enter a title for the Function Key part. A description is not necessary bu

Página 65

Using and Creating Keypads 149 To create a sample keypad entry screen: 1. Start a New project file in EasyBuilder-5000. 2. From the Objects menu

Página 66

150 EZware5000 Series Programming Manual Editing data registers using a keypad: 1. Save and compile the new project, then test the operation of t

Página 67

Using and Creating Keypads 151 5. Click OK and place the Direct Window Object anywhere on the window. 6. From the Window menu, select Open Window

Página 68

8 EZware5000 Series Programming Manual The X-models (HMI5104XH, HMI5121X, and HMI5150X) have an additional icon in the System Setup Toolbar for Scr

Página 69

152 EZware5000 Series Programming Manual Chapter 10 – Bar Graphs, Meters, and Trends This chapter focuses on three special graphic objects, whic

Página 70

Bar Graphs, Meters, and Trends 153 2. Use the Description: box to enter a title for the Bar Graph object. A description is not necessary but does

Página 71

154 EZware5000 Series Programming Manual 6. The Bar color/style determines the appearance of the Bar Graph. Function Description Frame Set the col

Página 72

Bar Graphs, Meters, and Trends 155 2. Use the Description: box to enter a title for the Meter Display object. A description is not necessary but

Página 73

156 EZware5000 Series Programming Manual 5. In the Degree section, you can select the range of your meter, where the range is 0 to 360. The Start

Página 74

Bar Graphs, Meters, and Trends 157 11. In the Value section, select the Zero and Span values. These are the PLC register values that represent th

Página 75

158 EZware5000 Series Programming Manual Creating Trend Displays and Data Sampling Objects Data Sampling objects can be used to log historical data

Página 76

Bar Graphs, Meters, and Trends 159 3. Description: Enter a name for the object. This isn't necessary, but will help in later identification

Página 77

160 EZware5000 Series Programming Manual 9. Enter a Description for the data format and then select the Data type. Click OK to return to the Data

Página 78

Bar Graphs, Meters, and Trends 161 2. In the Data Sampling Object Index, select the data sampling object from the drop down menu whose data is t

Página 79

HMI Local Setup 9 6. If using a static IP address, use the IP Address get from below option. The IP fields are enabled. Enter the appropriate sett

Página 80

162 EZware5000 Series Programming Manual 9. Select the Frame color and the Background color for the trend from the drop down menus. 10. Check th

Página 81

Bar Graphs, Meters, and Trends 163 13. In the Data sampling object section, select the channels you want to display by clicking the checkboxes un

Página 82

164 EZware5000 Series Programming Manual The HMI reads from the Sampling Object datalog file (*.dtl) immediately after the screen that contains th

Página 83

Bar Graphs, Meters, and Trends 165 2. Data Sampling Object index: Select from drop-down list which data file to use. Data files are created using

Página 84

166 EZware5000 Series Programming Manual Data Format tab: Used to configure how the data appears for each column: 1. Channel: Channels are confi

Página 85

Bar Graphs, Meters, and Trends 167 Title tab: Used to configure a title bar or legend at the top of the data columns: 1. Use title: Check to use

Página 86

168 EZware5000 Series Programming Manual Chapter 11 – Capturing Alarms and Events This chapter looks at how the Silver Series uses alarms and even

Página 87

Capturing Alarms and Events 169 2. Click the New... button. The Alarm (Event) Log Properties dialog appears. 3. On the General tab, set the Cate

Página 88

170 EZware5000 Series Programming Manual 9. Click the Message tab to display the Message dialog. 10. Enter the message to display when the alarm

Página 89

Capturing Alarms and Events 171 Displaying Alarms using the Alarm Display Object Though the Alarm (Event) Log Object continuously monitors the PLC

Página 90

10 EZware5000 Series Programming Manual 10. Configure your password settings. Local Password The password required to enter local setup. Upload P

Página 91

172 EZware5000 Series Programming Manual 4. Include categories: To include all categories, set this at 0 to 0. 5. Acknowledge style: Select eith

Página 92

Capturing Alarms and Events 173 Displaying Alarms using the Alarm Bar Object The Alarm Bar Object displays alarms scrolling horizontally along a si

Página 93

174 EZware5000 Series Programming Manual 7. Select the format for how the date and time is displayed in the Date: and Time: drop-down boxes. 8. C

Página 94

Capturing Alarms and Events 175 To create an Event Display Object: 1. From the Objects menu, click Alarm > Event Display or click the Event

Página 95

176 EZware5000 Series Programming Manual 5. Click on the Event Display tab to display the Event Display dialog. 6. Include categories: To inclu

Página 96

Security 177 Chapter 12 – Security The security feature in EasyBuilder-5000 allows you to create up to 12 users with individual passwords and assig

Página 97

178 EZware5000 Series Programming Manual In order for a user to login, they must first enter their user number into reserved local word LW9219. The

Página 98

Security 179 Object Security Many objects in EasyBuilder-5000 can be secured using the Security tab in the object’s properties window. For example,

Página 99

180 EZware5000 Series Programming Manual Display warning message if access denied: This option causes the message in Window 7 (Password Restriction

Página 100

Security 181 When Interlock is enabled, the following options are available: Hide when disabled: When this box is checked, the object is invisibl

Página 101

HMI Local Setup 11 13. Click on the HMI name tab to give the HMI a unique name. This name can be used to address the HMI for downloading over Ethe

Página 102

182 EZware5000 Series Programming Manual Auto logout There is an Auto logout feature in the System Parameters on the System Setting tab (Edit >

Página 103

Security 183 Additional Security Features Project Password (MTP file) Enable the Project Password in the System Parameter settings (Edit > Syste

Página 104

184 EZware5000 Series Programming Manual A developer can set the HMI key in the reserved local memory of the HMI (LW9046 configured for 32-bit unsi

Página 105

Security 185 XOB Password A project (*.mtp) must be compiled (*.xob) before it can be downloaded to an HMI. When compiling a project, you have the

Página 106

186 EZware5000 Series Programming Manual Decompiling Prohibited Click the Decompilation is prohibited checkbox in the Compiling window to prevent t

Página 107

Security 187 System Passwords The System Setup Toolbar in the HMI has the option of changing several passwords from their default setting of 111111

Página 108

188 EZware5000 Series Programming Manual To change a system password, the new password must be entered, and then entered again to confirm. As the p

Página 109 - Easy Converter

Security 189 Upload Password: The password required to upload data from the HMI to a PC or memory module. Upload to a PC using Project Manager Up

Página 110

190 EZware5000 Series Programming Manual Download Password: The password required to download data to the HMI from a PC or memory module. Download

Página 111

Security 191 Upload (History) Password: The password required to upload history files from the HMI to a memory module. Upload to a USB Flash or SD

Página 112

ii EZware5000 Series Programming Manual COPYRIGHT NOTICE This manual is a publication of Maple Systems, Inc., and is provided for use by its custom

Página 113

12 EZware5000 Series Programming Manual 15. Click the VNC server setting tab to enable remote access using VNC (Virtual Network Computing). Click

Página 114 - EasyPrinter

192 EZware5000 Series Programming Manual Chapter 13 – Using the Modbus Gateway The Modbus Gateway allows any ModbusTCP Master to request HMI data u

Página 115

Security 193 Configuring the Modbus Gateway 1. Configure the PLC to which Modbus registers will be mapped. Refer to the System Parameter Setting

Página 116

194 EZware5000 Series Programming Manual This example will show how to use the Modbus Gateway to obtain data from an Animatics Smartmotor. 1. Cli

Página 117

Security 195 3. Click the Add button to map a Modbus register. In this example, Modbus registers are being mapped to array elements in an Animati

Página 118

How to Reach UsCorporate HeadquartersWatlow Electric Manufacturing Company12001 Lackland RoadSt. Louis, MO 63146Sales: 1-800-WATLOW2Manufacturing Supp

Página 119

HMI Local Setup 13 The Popup download window option allows you to turn on or off whether the Download dialog window appears on the screen when a US

Página 120 - Simulation Settings

14 EZware5000 Series Programming Manual 3. Click on the Version tab to display the current firmware information. Transferring Projects and Data f

Página 121 - Pass-through mode

HMI Local Setup 15 When Download is selected, a dialog will appear requesting the Download password and what data to download. Password Enter th

Página 122

16 EZware5000 Series Programming Manual Chapter 3 – Connect the HMI to the PLC or Controller The Silver Series family of HMIs can connect to one,

Página 123

Connect the HMI to the PLC or Controller 17 Figure 3: COM Ports for the HMI5070NH/TH, HMI5100N/T, HMI5104TH/HMI5104XH/HMI5121X/HMI5150X 1010

Página 124 - Chapter 7 – Creating Windows

18 EZware5000 Series Programming Manual Figure 4: COM Ports for the HMI5056N 1010-1007, Rev. 10

Página 125 - Creating a New Window

Connect the HMI to the PLC or Controller 19 Figure 5: COM Port for the HMI5043N/T 1010-1007, Rev. 10

Página 126

20 EZware5000 Series Programming Manual Connecting to COM1 and COM3 on Port A Maple Systems Silver Series family of HMIs is capable of connecting t

Página 127 - Window Settings

Connect the HMI to the PLC or Controller 21 Scenario 2 – One RS485 2 Wire PLC/Controller with COM3 configured for RS485-2 Wire and one RS485 4 Wire

Página 128 - Monopoly Feature

EZware5000 Series Programming Manual iii Important Information Regarding Watlow Part Numbers When you purchased your Operator Interface Terminal an

Página 129 - Assigning Underlay Windows

22 EZware5000 Series Programming Manual Scenario 3 – One RS485 4 Wire PLC/Controller with COM1 configured for RS485-4 Wire and one RS232 PLC/Contro

Página 130 - Window Background

Connect the HMI to the PLC or Controller 23 Scenario 4 – One RS485 2 Wire PLC/Controller with COM1 configured for RS485-2 Wire and one RS232 PLC/Co

Página 131 - Using Base Windows

24 EZware5000 Series Programming Manual Connecting to COM1 and COM2 on Port B Two RS232 PLC/Controllers, with COM1 and COM2 configured for RS232.

Página 132 - Using the PLC

Connect the HMI to the PLC or Controller 25 Connecting multiple PLC/controllers serially using daisy chaining The RS485 4-wire and RS485 2-wire com

Página 133

26 EZware5000 Series Programming Manual Troubleshooting The HMI must be connected to a PLC/controller in order for the project to run correctly in

Página 134

Creating a Sample Project 27 Chapter 4 – Creating a Sample Project Often the best way to learn about new software is to jump righ

Página 135

28 EZware5000 Series Programming Manual 2. Click New… The Select Window Style dialog box appears. 3. Click Base Window. The Window Settings dia

Página 136

Creating a Sample Project 29 5. Click the box for the Background color. The color palette box opens. Click on the white color box

Página 137 - Using the Common Window

30 EZware5000 Series Programming Manual 5. Select shape number 7 and click OK. The Function Key Object’s Shape tab now shows a preview of how the

Página 138

Creating a Sample Project 31 7. In the top menu bar in EasyBuilder 5000, click Draw > Text (or select the Text Tool icon in t

Página 139

iv EZware5000 Series Programming Manual This page intentionally left blank 1010-1007, Rev. 10

Página 140

32 EZware5000 Series Programming Manual Now let’s create a bargraph on Window 11. We will use the bargraph to indicate the level of a tank. We wil

Página 141

Creating a Sample Project 33 3. Click the Outline tab. In the Attribute section, select the following: Type: Normal Direction: Up

Página 142

34 EZware5000 Series Programming Manual 8. Click the Picture Library… button and select the Tanks1 library. If it does not appear in the Library

Página 143

Creating a Sample Project 35 10. Click OK to accept the properties settings. On the main screen of EasyBuilder you will see a whi

Página 144

36 EZware5000 Series Programming Manual 3. In the Attribute section, select the following: Set Style: Press and hold increment (JOG++) (this

Página 145 - System Message Windows

Creating a Sample Project 37 12. Click OK and place the Set Word Object below the bargraph on Window 11 in EasyBuilder. You can c

Página 146

38 EZware5000 Series Programming Manual 16. Paste the Set Word Object to the window (Edit > Paste or Ctrl+V) and drag it next to the other Set

Página 147

Creating a Sample Project 39 19. In the Attribute section, select the following: Set Style: Press and hold decrement (JOG--)

Página 148

40 EZware5000 Series Programming Manual 3. In the Blinking section, select None for the Mode. 4. Click the Shape tab and check the Use Picture c

Página 149 - Using the Tag Library

Creating a Sample Project 41 6. Click OK and place the Bit Lamp Object to the left of the tank. You can click and drag it to adj

Página 150 - Creating the Label Library

EZware5000 Series Programming Manual v Table of Contents COPYRIGHT NOTICE ... ii WARRANTY ...

Página 151

42 EZware5000 Series Programming Manual 11. Click the Profile tab and set the Width to 100 and the Height to 25 (pixels). 12. Click OK to accept

Página 152

Creating a Sample Project 43 3. Click the Shape tab and deselect the Use Shape checkbox. This will make the Set Bit invisible on

Página 153 - Using the Label Library

44 EZware5000 Series Programming Manual 4. Click OK and place the Set Bit Object on the window. It will appear as a square frame. Click on the scr

Página 154

Creating a Sample Project 45 2. Use the drop-down menus to locate the project folder in EZ5000. 3. In the File name text box, ty

Página 155 - How to Create a Keypad

46 EZware5000 Series Programming Manual 2. Click the arrow button to go to the next window. 3. Click and hold the arrow UP button to fill the ta

Página 156

Creating a Sample Project 47 Downloading your first project First, connect a +24 VDC power supply to the HMI. Refer to the Silver

Página 157

48 EZware5000 Series Programming Manual 3. Select Tools > Download from EasyBuilder’s menu (or click the Download icon). 4. Make sure that the

Página 158

Simulator Mode 49 Chapter 5 – Simulator Mode As you saw from creating the sample project in the last chapter, downloading any

Página 159

50 EZware5000 Series Programming Manual Off-line simulation is also great for demonstrating the operation of the HMI and becoming familiar with the

Página 160 - Creating Bar Graphs

Simulator Mode 51 2. Click Online-Simulator. The Open Project dialog box appears. 3. Click on the compiled project file that

Página 161

vi EZware5000 Series Programming Manual To use on-line simulation mode from EasyBuilder ...

Página 162 - Creating Meter Displays

52 EZware5000 Series Programming Manual Chapter 6 – Using EZware-5000 Overview The EZware-5000 software is composed of three separate applications

Página 163

Using EZware-5000 53 HMI IP, Password Settings Settings Button Click the Settings button to view the Download/Upload passwords (default 111111). T

Página 164

54 EZware5000 Series Programming Manual EasyBuilder-5000 Development Window Objects Summary EasyBuilder includes several active graphics objects

Página 165

Using EZware-5000 55 Set Bit The Set Bit Object is used as a button to toggle ON or OFF the state of a bit or coil in the PLC, or a bit in the HM

Página 166

56 EZware5000 Series Programming Manual Function Key The Function Key Object is used to change windows, popup a window, return to a previous wind

Página 167

Using EZware-5000 57 Moving Shape The Moving Shape Object is used to move a shape or picture on the screen based on values in consecutive registe

Página 168

58 EZware5000 Series Programming Manual Recommended Format and Resolution 100% (1:1) 50% (1:2) NTSC 720 x 480 360 x 240 PAL 720 x 576 360 x 288 A

Página 169

Using EZware-5000 59 History Data Display The History Data Display Object is used to display historical data collected by the Data Sample Object

Página 170

60 EZware5000 Series Programming Manual The number of data points must be stored at [control word address + 1], and the data must be stored startin

Página 171 - History Data Display

Using EZware-5000 61 The Read address field is the starting address of the data to plot. Each channel has its own Read address. Normally, the X and

Página 172

EZware5000 Series Programming Manual vii Creating Bar Graphs ... 152 Creating Meter Displays ...

Página 173

62 EZware5000 Series Programming Manual Line: The data is plotted as a Line graph, with squares plotted at each data point. Point: The data is plot

Página 174

Using EZware-5000 63 to display (including the starting day). If three days are selected, but only two event files are included within the three da

Página 175

64 EZware5000 Series Programming Manual Backup The Backup Object is used to copy recipe files (*.rcp), event files (*.evt), and data files (*.dtl

Página 176 - Using Alarms

Using EZware-5000 65 Trigger address + 1 Number of words to transfer (32 words maximum) The number of words to transfer from the PLC to the HMI or

Página 177

66 EZware5000 Series Programming Manual Note: When transferring bits, bits can only be transferred to the local HMI’s internal memory. It is not po

Página 178

Using EZware-5000 67 Action modes include Bit ON, Bit OFF, or Word write. Bit ON: Start action sets the Action address bit. End action clears the A

Página 179

68 EZware5000 Series Programming Manual Time setting address + 8 End time (hour) This register determines the hour the End Action is executed. Rang

Página 180

Using EZware-5000 69 Managing Projects Like most Windows™ application software, EasyBuilder will open, save, close, and print files using the stand

Página 181

70 EZware5000 Series Programming Manual 3. Enter a file name and then click Save. 4. The main screen of EasyBuilder reappears. To save a project

Página 182 - Using Events

Using EZware-5000 71 Note: It is a good idea to backup your Library folder before uncompressing a *.cmp file because the uncompress utility will ov

Página 183

viii EZware5000 Series Programming Manual This page intentionally left blank 1010-1007, Rev. 10

Página 184

72 EZware5000 Series Programming Manual 2. The Object List combines a list of all of the windows in a project, and all of the objects on each wind

Página 185 - Chapter 12 – Security

Using EZware-5000 73 Using the Window Tree to change object attributes 1. On the Window Tree, click + adjacent to any window number. The tree will

Página 186

74 EZware5000 Series Programming Manual  If you still don’t see the grid after you have enabled it, make sure that the color of the grid doesn’t m

Página 187 - Object Security

Using EZware-5000 75 To zoom in on the selected window 1. Use the zoom pull-down menu in the Edit Toolbar. Zoom levels range from 50% to 200% in

Página 188 - Interlock

76 EZware5000 Series Programming Manual Basic Editing Commands To select a graphics object 1. On the Edit Menu, click Select or click the mous

Página 189

Using EZware-5000 77 3. From the Edit menu, click Undo or click the Undo icon from the Standard Toolbar. You can also press CTRL+Z. The deleted te

Página 190 - Auto logout

78 EZware5000 Series Programming Manual Multiple objects can be created according to these parameters: Pitch vs. Interval: This setting affects how

Página 191 - Additional Security Features

Using EZware-5000 79 4. In the Destination box, enter the number of the window in the current project that you wish to copy the selected window(s)

Página 192 - Disable Upload Function

80 EZware5000 Series Programming Manual 4. All of the objects that use PLC data registers or the internal memory of the HMI are listed in this di

Página 193 - XOB Password

Using EZware-5000 81 Bottom Layer: Send the selected object to the bottom layer. Previous Layer: Moves the selected object to the previous layer

Página 194 - Decompiling Prohibited

Introduction 1 Chapter 1 – Introduction Welcome Welcome to the Maple Systems’ Silver Series Operator Interface Terminals (OITs) from Watlow. Using

Página 195 - System Passwords

82 EZware5000 Series Programming Manual To make objects the same size : 1. Select the objects you wish to make the same size. 2. From the Edit

Página 196

Using EZware-5000 83 To rotate objects : 1. Select the object you wish to rotate. 2. From the Edit menu, select Flip/Rotate > Rotate 90 Deg

Página 197

84 EZware5000 Series Programming Manual System Parameter Settings The final section of this chapter shows all the settings or parameters that can b

Página 198

Using EZware-5000 85 To configure Device tab settings: 1. Click the New… button. The Device Properties dialog appears.  You can “export” a proj

Página 199 - 1010-1007, Rev. 10

86 EZware5000 Series Programming Manual 6. Select the PLC station number for your PLC if appropriate (see Controller information Sheet for your PL

Página 200

Using EZware-5000 87 To configure the Model tab settings: 1. HMI model: Select the HMI model that you are programming. 2. HMI station no.: When

Página 201

88 EZware5000 Series Programming Manual Auto Resizing Using the Model Tab This tab can be used to automatically resize your project when changing

Página 202

Using EZware-5000 89 To configure General tab settings: 1. Fast selection button: The Attribute: drop-down enables or disables the fast selectio

Página 203

90 EZware5000 Series Programming Manual 3. Options: The Startup window no. selects the window number that will be displayed every time the HMI is

Página 204 - SATISFACTION

Using EZware-5000 91 To configure System Setting tab settings: 1. Startup language after redownloading the project: Select the language that the