72 CLS Users Guide
Setup
RTD Ranges (4 and 8CLS)
Pulse Sample Time
You can connect a digital pulse signal of up to 2 KHz to the controller's
pulse input. In this menu, you specify the pulse sample period. (This is
the second menu of the Set up Loop Inputs menu for the pulse input
loop only.) Every sample period, the number of pulses the controller
receives is divided by the sample time. The controller scales this
number and uses it as the pulse loop's process variable.
Selectable Range:
1-20 seconds.
Loop Name
Use this menu to name your loop using two-characters. After specifying
a new name, it is placed on the single loop display instead of the loops
number.
Input Units
Use this menu to choose a three-character description of the loops
engineering units
Name Range in
º
F Range in
º
C Resolution
Probe
Temp. In
º
C
Accuracy: 25
º
C
Ambient
º
C
º
F
Accuracy: 0-
50
º
C Ambient
º
C
º
F
RTD1 -148.0 to
527.0
-100.0 to
275.0
0.023
º
C
25 ±0.35 ±0.63 ±0.5 ±0.9
275 ±1 ±1.8 ±1.5 ±2.7
RTD2 -184 to
1544
-120 to 840
0.062
º
C
25 ±0.9 ±1.62 ±2.8 ±5.04
840 ±1.1 ±1.98 ±4.3 ±7.74
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
05 INPUT PULSE
SAMPLE TIME ? 1s
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
A5 LOOP
NAME ? A5
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
02 INPUT
UNITS ?
º
F