Vista de página 7
8
WATLOW DIN-A-MITE Style C User's Manual
Unit Dimensions - Through-Wall (Cabinet Panel)
ç
Ó
3
5
Mounting
Mounting procedure
for UL® 50 Type 4X
Enclosure and UL® /
ANSI 12.12.01 Through-
wall mount models
Materials included:
(1) Silicone gasket
(8) M5 screws and
lockwashers
(1) DIN-A-MITE C
through-wall
1. Drill and cut the
panel as shown in
the dimensioned
drawing at right.
2. Remove the
mounting screws
from the heatsink.
3. Peel off the
protective film from
the silicone
gasket. Stick the
gasket to the
heatsink so the
gasket holes line up
with the screw holes
in the heatsink.
4. Mount the heatsink
vertically. Torque to
2.26 to 2.82 Nm (20
to 25 in-lb).
Top
114 mm
(4.50 in)
57 mm (2.25 in)
outside
(any gauge)
55 mm (2.17 in)
inside
(12 gauge)
Front panel is touch-safe,
no clearance is required.
Sheet Metal (12 gauge)
Ground lug (2-8 GA
M5 (0.8 by 10 mm) (8)
M5 Internal Tooth Lock Washer (8)
included
178 mm (7.00 in)
122 mm (4.81 in)
Panel
Opening
Outline
102 mm (4.0 in) minimum
clearance for air flow 
(top and bottom)
10 mm (0.4 in) minimum
clearance for air flow 
(both sides)
Front
123
456
Typical Panel Opening
Heatsink Outline
7.0 mm (0.275 in)
26.3 mm (1.034 in)
78.8 mm
(3.103 in)
98.1 mm
(3.862 in)
105.1 mm
(4.137 in)
10.8 mm (0.425 in)
41.3 mm
(1.625 in)
117.5 mm
(4.625 in)
148.6 mm
(5.850 in)
161.9 mm
(6.375 in)
Drill 5.8 mm (0.228 in) (8)
8.6 mm (0.338 in) Reference
9.5 mm (0.375 in) Reference