EZ-ZONE PM Limit Express • 29 • Setup Menu
Setup Menu (cont.)
Display Parameter Name Description Range (Defaults are shown bold)
[`A;LA]
[ A.LA]
Alarm Latching
Turn alarm latching on or off. A latched alarm
has to be turned off by the user.
Appears if: When alarm type is set to process.
[nLAt] Non-Latching
[`LAt] Latching
`A;bL]
[ A.bL]
Alarm Blocking
Select when an alarm will be blocked. After
startup and/or after the set point changes,
the alarm will be blocked until the process
value enters the normal range.
Appears if: When alarm type is set to process.
[`oFF] Off
[`Str] Startup
[StPt] Set Point
[both] Both
[`A;si]
[ A.Si]
Alarm Silencing
Turn alarm silencing on to allow the user
to disable the output tied (configured) to
this alarm
Appears if: Always.
[`oFF] Off
[``on] On
[A;dSP]
[A.dSP]
Alarm Display
Display an alarm message when an
alarm is active.
Appears if: When alarm type is set to process.
[`oFF] Off
[``on] On
[PAr1]
[PAr1]
Upper or Left Display
Select parameter to display.
Appears if: Always.
[AC;Pu]
Active Process Value
[none] None
[PAr2]
[PAr2]
Lower or Right Display
Select parameter to display.
Appears if: Always.
[`Ls;t]
Limit State
[`A;hi]
Alarm High Set Point
[`Lh;S]
Limit High Set Point
[`A;lo]
Alarm Low Set Point
[`LL;S]
Limit Low Set Point
[none] None
[`ad;s]
[ Ad.S]
Zone Address - Standard Bus Com-
munication
Set zone address from 1-16.
Appears if: Always.
1-16
1