Watlow EZ-ZONE RUI/Gateway Manual do Utilizador Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 62
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 8
Ó
Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.
Watlow EZ-ZONE
®
RUI/Gateway 6 Chapter 2 Install and Wire
Power
Power
power
power
98
99
CF
CD
CE
B5
D6
D5
Slot C
long case
fuse
Power
power
power
98
99
CF
CD
CE
B5
D6
D5
Slot C
short case
fuse
• Minimum/Maximum Ratings
• 85 to 264VÅ (ac)
• 20.4 to 26.4 Vı (ac/dc)
• 47 to 63Hz
• 6VA maximum
Standard Bus EIA-485 Communications
Standard Bus
EIA-485
T-/R-
common
98
99
CF
CD
CE
B5
D6
D5
Slot C
long case
T+/R+
Standard Bus
EIA-485
T-/R-
common
98
99
CF
CD
CE
Slot C
short case
T+/R+
• WireT-/R-totheAterminaloftheEIA-485port.
• WireT+/R+totheBterminaloftheEIA-485port.
• WirecommontothecommonterminaloftheEIA-485
port.
• Donotroutenetworkwireswithpowerwires.Connect
network wires in daisy-chain fashion when connecting
multiple devices in a network.
• Donotconnectmorethan16controllersonanetwork.
• maximumnetworklength:1,200meters(4,000feet)
• 1/8thunitloadonEIA-485bus
Note:
Disconnect any USB to EIA-485 converter when not
connected to a PC (without power). Failure to do so
may cause communications errors.
EIA-232/485 Modbus RTU Communications
485 common
485 T+/R+
CB
CA
CC
CB
CA
C5
C3
C2
Slot B
485 T-/R-
485 T+/R+
485 T-/R-
232 common
232 (TX) to DB9 pin 2 (RD)
232 (RD) to DB9 pin 3 (TX)
•WireT-/R-totheAterminal
of the EIA-485 port.
• WireT+/R+totheBtermi-
nal of the EIA-485 port.
• Wirecommontothecom-
mon terminal of the EIA-
485 port.
• Donotroutenetworkwires
with power wires. Connect
network wires in daisy-
chain fashion when connect-
ing multiple devices in a
network.
• Aterminationresistormay
be required. Place a 120 Ω
resistoracrossT+/R+and
T-/R- of last controller on
network.
• DonotwiretoboththeEIA-
485 and the EIA-232 pins at
the same time.
• TwoEIA-485terminalsof
T/R are provided to assist in
daisy-chain wiring.
• Donotconnectmorethan
one EZ-ZONE
®
RUI on a
EIA-232 network.
• MaximumnumberofEZ-
ZONE
®
RUI on a Modbus
®
RTU EIA-485 network: 247
• MaximumEIA-232network
length: 15 meters (50 feet)
• MaximumEIA-485network
length: 1,200 meters (4,000
feet)
• 1/8thunitloadonEIA-485
bus.
EZK _-_ 2 _ _-A _ A A
Modbus-IDA
Terminal
EIA/TIA-485
Name
Watlow Termi-
nal Label
Function
DO A CA or CD T-/R-
D1 B CB or CE T+/R+
common common CC or CF common
Note:
Disconnect any USB to EIA-485 converter when not connected to a PC
(without power). Failure to do so may cause communications errors.
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 61 62

Comentários a estes Manuais

Sem comentários