Watlow Series SD31 27 Chapter 5 Setup
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
** Timer model only (SD31-XXXX-XTXX)
Caution: Writing to registers continuously, such as ramping set points via comms, will damage the SD31 EEPROM memory. See page 59.
[Lgc2]
[Lgc2]
Alarm 2 Logic
Select the alarm output condition in the
alarm state.
[AL`C]
closed on alarm
[AL`O]
open on alarm
[AL`C] [Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[LAt2]
[LAt2]
Alarm 2 Latching
Turn alarm latching on or off.
[nLAt]
non-latching - off
[`LAt]
latching - on
[nLAt] [Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[SiL2]
[SiL2]
Alarm 2 Silencing
Turn alarm silencing on or off.
[`OFF]
off - no silencing
[``On]
on - silencing
[`OFF] [Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[dSP2]
[dSP2]
Alarm 2 Message
Displays an alarm message when an
alarm is active.
[`OFF]
off - no message
[``On]
on - message
[``On] [Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[ACLF]
[ACLF]
AC Line Frequency
Set the frequency of the applied AC line
power source.
[``50]
50 (0)
[``60]
60 (1)
[``60]
(1)
276 R/W
If [Ctr1] or [Ctr2] is
set to {
Urtb]
.
[Unit]
[Unit]
Units of Measurement
Set the type of units used for the PID con-
trol parameters.
[``US]
US (0)
[``SI]
SI (1)
[``US]
(0)
45 R/W
Always active.
[I;Err]
[I.Err]
Input Error Latching
Turn input error latching on or off.
[nLAt]
non-latching (0) - off
[`Lat]
latching (1) - on
[nLAt]
(0)
90 R/W
Always active.
[FAIL]
[FAIL]
Input Error Failure Mode
Set the input error failure mode when an
error is detected and the control changes
to manual mode.
[`OFF]
off (0) - 0% power
[bPLS]
bumpless (1) -
current power level
[Man]
manual (2) - fixed
power level
[bPLS]
(1)
252 R/W
Always active.
[MAn]
[MAn]
Input Error Power
Set the manual power level when an in-
put error causes a change to manual
mode.
-100.0 to 100.0%
(-10000 to 10000)
0.0%
253 R/W
[FAIL}
is set to
[Man]
.
[`dSP]
[ dSP]
Display Default
Select which display appears normally
and which display requires pressing the
ß Key to access.
[`Set]
set point normally
appears, press ß Key to
view process value (0)**
[`Pro]
process normally ap-
pears, press ß Key to
view set point value (1)**
[aC;Ti]
timer normally ap-
pears, press ß key to
view process value (2)**
[ti;Ac]
process normally ap-
pears, press ß key to
view timer value (3)**
[ti;SP]
set point normally
appears, press ß Key to
view timer value (4)**
[to;tt]
press ß key to
toggle between process and
timer values (5)**
[~Pro]
(1)
44 R/W
Always active.