Watlow Series SD6 Limit with DeviceNet 15
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
152 Get/Set Alarm 2 Message BOOLEAN Display an alarm message
when an alarm is active.
(0) OFF (no message)
(1) ON (default)
153 Get/Set Upper Display Look USINT Select what value appears in
the upper display
(0) - None
(1) - Process
(2) - Limit 1 low
(3) - Limit 1 high (default)
(4) - Limit 2 low
(5) - Limit 2 high
(6) - Alarm 2 Low
(7) - Alarm 2 High
154 Get/Set Lower Display Look USINT Selects what value appears
in the lower display
(0) - None
(1) - Process
(2) - Limit 1 low
(3) - Limit 1 high (default)
(4) - Limit 2 low
(5) - Limit 2 high
(6) - Alarm 2 low
(7) - Alarm 2 high
155 Get Analog Input Error
Latching
BOOLEAN Select whether input errors
are latched.
(0) Non-latching (default)
(1) Latching
161 Get/Set Lockout USINT Set the security level for the
user interface.
(0) No Lockout (default)
(1) Programming and
setup page locked
(2) Programming and
setup page locked. Only
limit setpoints accessible
(3) Full lockout
162 Set Limit Acknowledge for
output 1
BOOLEAN Clears limit condition for out-
put 1.
(0) No
(1) Yes
163 Set Limit or Alarm
Acknowledge for output 2
BOOLEAN Clears alarm or limit condi-
tion for output 2.
(0) No
(1) Yes
165 Get/Set Analog Input mV Scale
Low
DINT Sets low scale for millivolt
inputs.
5.00 to 50.00 mV
(default 5.00)
166 Get/Set Analog Input mV Scale
High
DINT Sets high scale for millivolt
inputs.
5.00 to 50.00 mV
(default 50.00)
167 Get/Set Process Milliamp Low
Error
DINT Sets the low threshold for
input errors when using milli-
amp inputs
1.00 to 10.00 mA
(default 1.00)
170 Get/Set Process Milliamp High
Error
DINT Sets the high threshold for
input errors when using milli-
amp inputs
10.00 to 20.00 mA
(default 20.00)