Watlow EZ-ZONE
®
PM Integrated Controller 28 Chapter 2 Install and Wire
Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation between
analog input 1, digital input-outputs,
switched dc/open collector outputs
and process outputs to prevent
ground loops.
Note:
The control output common termi-
nal and the digital common terminal
are referenced to different voltages
and must remain isolated.
Note:
This Equipment is suitable for use in
CLASS I, DIVISION 2, Groups A, B,
C and D or Non-Hazardous locations
only. Temperature Code T4A
Warning:
ç
Explosion Hazard - Dry contact clo-
sure Digital Inputs shall not be used
in Class I Division 2 Hazardous Loca-
tions unless switch used is approved
for this application.
Warning:
ç
Explosion Hazard – Substitution of
component may impair suitability
for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not discon-
nect while the circuit is live or
unless the area is known to be free
of ignitable concentrations of flam-
mable substances.
Example: Using a Current Transformer
Controller
Output N
CT Input
L2 L1
Fuse
SSR
3A x 4
12A
48mA
48mA
12A x 4 = 48A
Turns around CT
Turns around CT
CT Primary Current
CT Secondary Current
Total current
CT Ratio R = 1000:1
:
Is = IpT/R = 50mA
CSC = I
p(full scale) = 50mA(R)/T
CSI = Output N
I
s = Current in secondary of current transformer
I
p = Current in primary of current transformer
T = Number of turns through the primary of the transformer
R = Number of turns in the secondary of the current
transformer (Turns ratio, assuming one primary turn)
CSC = Current Scaling (parameter found in Current Menu
of Setup Page)
CSI = Current Source Instance (parameter found in Current
Menu of Setup Page)
Digital Output 5 - 6
common
switched dc
switched dc
98
99
CF
CD
CE
B5
D6
D5
Slot C
Digital Output
• Updaterate10Hz
• Outputvoltage24V
• Currentlimit,Output5,24
mA maximum
• Currentlimit,Output6,
10 mA maximum driving
single pole DIN-A-MITE
• *Capableofdrivinga3-pole
DIN-A-MITE
• Open-circuitvoltage22to
32VÎ (dc)
PM _ _ [2,4] _ _-_ _ _ _ _ _ _
* Output 5 only
VDC
switched dc outputs
Internal Circuitry
D5
D6
B5
Quencharc Note:
Switching pilot duty inductive loads
(relay coils, solenoids, etc.) with the
mechanical relay, solid state relay or
open collector output options requires
use of an R.C. suppressor.