Watlow EZ-ZONE PM Manual do Utilizador Página 23

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 111
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 22
Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation be-
tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.
Note:
The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.
Watlow EZ-ZONE
®
PM Limit Controller 20 Chapter 2 Install and Wire
Input 1 Thermocouple
-
+
Thermocouple
(Input 1)
L1
K1
J1
L2
K2
T1
S1
R1
Slot A
• 2KΩmaximumsourceresistance
• >20MΩinputimpedance
• 3microampereopen-sensordetection
• Thermocouplesarepolaritysensitive.Thenegativelead(usually
red)mustbeconnectedtoS1.
• Toreduceerrors,theextensionwireforthermocouplesmustbe
of the same alloy as the thermocouple.
Input1:PM_ _ _ _ _ - _ _ _ _ _ _ _(S1/R1)
Input 1 RTD
2-wire
RTD
(Input 1)
L1
K1
J1
L2
K2
T1
S1
R1
S1
S3
Slot A
3-wire
RTD
(input 1)
L1
K1
J1
L2
K2
T1
S1
R1
S1
S2
S3
Slot A
• platinum,100and1,000Ω@0°C
• calibrationtoDINcurve(0.00385Ω/Ω/°C)
• 20Ωtotalleadresistance
• RTDexcitationcurrentof0.09mAtypical.Each
ohm of lead resistance may affect the reading by
0.03°C.
• For3-wireRTDs,theS1lead(usuallywhite)must
beconnectedtoR1.
• Forbestaccuracyusea3-wireRTDtocompensate
for lead-length resistance. All three lead wires must
have the same resistance.
PM _ _ _ _ _-_ _ _ _ AAA (all)
Input 1 Process
-
+
L1
K1
J1
L2
K2
T1
S1
R1
volts
Process
(Input 1)
Slot A
-
+
T_
S_
amperes
Slot A
• 0to20mA@100Ωinputimpedance
• 0to10VÎ(dc)@20kΩinputimpedance
• 0to50mVÎ(dc)@20kΩinputimpedance
• scalable
PM _ _ _ _ _-_ _ _ _ AAA (all)
Input 1 Potentiometer
pot
(input 1)
L1
K1
J1
L2
K2
T1
S1
R1
Slot A
CW
CCW
• Usea1kΩpotentiometer.
PM _ _ _ _ _-_ _ _ _ AAA (all)
Vista de página 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 110 111

Comentários a estes Manuais

Sem comentários