Watlow EZ-ZONE
®
PM Limit Controller 48 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1)
Sensor Type
Set the analog sensor
type to match the device
wired to this input.
Note:
There is no open-sensor
detec-
tion for process inputs.
[`oFF] Off (62)
[``tC] Thermocouple (95)
[`mu] Millivolts (56)
[uolT]Voltsdc(104)
[`MA]
Milliampsdc(112)
[r0;1H]RTD100Ω(113)
[r1;0H]RTD1,000Ω(114)
[`Pot]Potentiometer1kΩ
(155)
[thEr] Thermistor (229)
Off Instance 1
Map 1 Map 2
368 368
0x68(104)
1
5
3 4005 uint
RWES
[`Lin]
[ Lin]
Analog Input (1)
TC Linearization
Set the linearization to
match the thermocouple
wired to this input.
[```b]B(11) [```H] K (48)
[```C]C(15) [```n] N (58)
[```d]D(23) [```r] R (80)
[```E] E (26) [```S] S (84)
[```F]F(30) [```t]T(93)
[```J] J (46)
J
Instance 1
Map 1 Map 2
370 370
0x68(104)
1
6
4 4006 uint
RWES
[`Rt;L]
[ rt.L]
Analog Input (1)
RTD Leads
Set to match the num-
berofleadsontheRTD
wired to this input.
[```2] 2(1)
[```3] 3(2)
2 Instance 1
Map 1 Map 2
372 368
0x68(104)
1
7
- - - - 4007 uint
RWES
[Unit]
[Unit]
Analog Input (1)
Units
Set the type of units the
sensor will measure.
[`A;tP] Absolute Temperature
(1540)
[``rh] Relative Humidity
(1538)
[`Pro] Process (75)
[PWr] Power(73)
Process Instance 1
Map 1 Map 2
- - - - 442
0x68(104)
1
0x2A (42)
5 4042 uint
RWES
[`S;Lo]
[ S.Lo]
Analog Input (1)
Scale Low
Set the low scale for
process inputs. This
value, in millivolts, volts
or milliamps, will corre-
spond to the Range Low
output of this function
block.
-100.0to1,000.0 0.0 Instance 1
Map 1 Map 2
388 388
0x68(104)
1
0xF(15)
6 4015 float
RWES
[`S;hi]
[ S.hi]
Analog Input (1)
Scale High
Set the high scale for
process inputs. This
value, in millivolts, volts
or milliamps, will cor-
respond to the Range
High output of this
function block.
-100.0to1,000.0 20.0 Instance 1
Map 1 Map 2
390 390
0x68(104)
1to4
0x10(16)
7 4016 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
* These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set