232 EZwarePlus Programming Manual
To add an HMI to the project:
1. Open the HMI Manager by clicking on the Objects menu and selecting HMI Manager, or by clicking on the
HMI Manager icon in the toolbar.
2. Click the Add button. Enter the IP address and Port No. of the HMI. The IP address of the HMI is configured
in the System Settings window in the HMI. The Port No. is configured in the EZwarePlus project’s System
Parameters > Model tab.
Check Use Local HMI to connect to an Online or Offline Simulator running on the PC. It will appear as Local
Host in the HMI Manager list. Click OK to add the HMI to the HMI Manager list.
3. Repeat to add more HMIs to the list. Click Exit when completed.