Watlow Series PD ■ 9 ■ Chapter 2 Install and Wire
Ó
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
ç
WARNING: Process input may
not have sensor break protec-
tion. Outputs can remain full on.
Note: Install a 1kΩ pull-down
resistor for each digital in-
put using voltage inputs.
Note: Install a 10kΩ pull-up re-
sistor for each digital input
using contact closure in-
puts.
Figure 9a — Input 1, 0 to 20 mA Process Input
(all model numbers)
• Input impedance 100 Ω, dc only
• Controller does not supply power for the current loop
Figure 9b — Input 2, 0 to 20 mA Process Input
PDD _-_ _ _ _-_ _ _
• Input impedance 100 Ω, dc only
• Controller does not supply power for the current loop
• Input 2 isolated from Input 1
Dual Digital Inputs
PD_ 1-_ _ _ _-_ _ _
• Input impedance 10kΩ, dc only
• Input 2 isolated from Input 1
Figure 9c — Voltage input
0-1VÎ (dc) Event Input Low State
2-36VÎ (dc) Event Input High State
Figure 9d — Contact closure
0-2kΩ Event Input Low State
> 7kΩ Event Input High State