Watlow Series PD ■ 17 ■ Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.
Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Note: A current transformer input
is not available if Output 1 or 3
is a process output.
Figure 17a — Output 3 Open Collector
PD_ _ - _ _ C _ - _ _ _ _
• Maximum current sink 250 mAÎ (dc)
• Maximum supply voltage 42VÎ (dc)
• Output does not supply power
Figure 17b — Output 3 Process
PD_ _ - _ _ F _ - _ _ _ _
• Analog output scalable from 0 to 10VÎ (dc) or 0 to 20 mAÎ (dc)
• Load capability: voltage, 1 kΩ minimum; current, 800 Ω maximum
• Output supplies power
• Cannot use voltage and current output at the same time
Figure 17c — Output 4 Mechanical Relay
PD_ _ - _ _ _ E - _ _ _ _
• Form C.contacts
• 2 A, resistive
• 125 VA pilot duty, 120/240VÅ (ac), inductive
• 240VÅ (ac) maximum
• 30VÎ (dc) maximum.
• See Quencharc note
• For use with ac or dc
• Minimum load current: 10 mA
• Output does not supply power
COM.
N.O.
N.C.
COM.
compliance.