Watlow Series PD 23 Chapter 5 Troubleshooting
Indication Probable Cause(s) Corrective Action
Alarm will not activate or
clear.
Controller is in Error condition.
Alarm is in latched setting.
Alarm is silenced.
Incorrect configuration.
Incorrect wiring.
Wrong output type.
Defective controller.
Determine cause of error and correct.
Wait for process to return to normal
and acknowledge alarm.
Wait for process to return to normal
and alarm will work correctly.
Configure Alarm, Alarm Set Point, Hys-
teresis, Silencing and Latching.
Correct wiring.
Replace controller with correct output
type.
Repair or replace controller.
Controller's process value
reading is decreasing as the
actual process is increasing.
Thermocouple is reversed wired.
Analog voltage or current input scal-
ing is reversed.
Check thermocouple wire for correct po-
larity.
Configure correct scaling on Input page.
Controller does not control
close enough to set point.
PID values incorrect.
Cycle times incorrect.
Heat or cooling capacity incorrectly
sized for application.
Incorrect sensor placement.
Controller is in Manual mode (open
loop).
Control loop action configured incor-
rect.
Tune controller (Auto Tune or Manual
Tune).
Set cycle time to match hardware on
Control Loop .
Size energy sources to match load.
Place sensor in optimal location.
Change to Auto mode (closed loop) on
Monitor page.
Configure Control Loop Action on Con-
trol Loop page.
Output cycles (turns on and
off) too frequently.
• Wrong control mode. PID control se-
lected instead of ON-OFF control.
• The cycle time is set too short.
• Activate ON-OFF control on Output
page.
• Increase Output Cycle Time on Out-
put page.
Cannot access Security, Mon-
itor, Configuration or Cali-
bration page.
Password is enabled and incorrect
password is supplied.
Provide the correct user name and pass-
word.
Process value reads incor-
rectly
Analog input is configured incorrectly.
• Thermocouple sensor shorted.
• Process sensor scaled incorrectly.
• Calibration offset is incorrect.
• Sensor is wired incorrectly.
• Controller calibration is incorrect or
corrupt.
• Defective controller.
• Configure control for appropriate sen-
sor input on Analog Input page.
• Repair wiring or replace sensor.
• Set scaling on Analog Input page.
• Correctly set calibration offset.
• Wire sensor per wiring section.
• Recalibrate controller.
• Repair or replace controller.