Watlow Series SD6 PID Controller with DeviceNet Addendum Manual do Utilizador Página 15

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 32
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 14
Watlow Series SD6 PID with DeviceNet 15
Attribute # Access Rule Name DeviceNet
Data Type
Description of Attribute Semantics of Values
121 Get/Set Set Point High Limit mA
and volts
DINT Set the high range for the
set point
Set Point Low Limit +
0.001 to 9999, if Input
Type = mA or Volt (default
= 9999)
(* 1000)
122 Get/Set Input Filter USINT Select filtering action (1) OFF (no filtering,
default)
(1) Filter display only
(2) Filter control input only
(3) Filter both
123 Get/Set Filter Value UDINT Set the input filter value, units
in seconds
0.0 to 60.0 (default = 0.0)
seconds (* 1000)
124 Get/Set Output 1 Function USINT Set the output 1 function (0) OFF
(1) Process Alarm
(2) Deviation Alarm
(3) Heat Control (default)
(4) Cool Control
125 Get/Set Control Method 1 USINT Set the output 1 control type
Only used with PID control
(1) Fixed Timed Base
(default)
(1) Variable Time Base
126 Get/Set Fixed Time Base 1 USINT Set the time base for fixed
time based control
1.0 to 60.0 if Output 1 is a
mechanical relay
0.1 to 60.0 if Output 1 is
not a mechanical relay
Defaults:
20.0 mechanical relay
5.0 solid-state relay
1.0 switched DC
127 Get/Set Power Limit 1 UINT Set the maximum power out-
put for a control output
0.0 to 100%
(default = 100%)
128 Get/Set Output Power Scale Low 1 USINT Set the low end of the range
within which the output will
scale
0 to 100%
(default = 0)
129 Get/Set Output Power Scale High 1 USINT Set the high end of the range
within which the output will
scale
0 to 100%
(default = 100)
130 Get/Set Output Non-linear Function
1
USINT Select a non-linear output
curve to match the response
of your system
(0) OFF (default)
(1) Curve 1
(2) Curve 2
131 Get/Set Analog Output 1 Units USINT Set the analog output units (0) Milliamperes (default)
(1) Volts
132 Get/Set Analog Output 1 Low Scale
mA
UDINT Set the low scale for analog
outputs
0.00 to 20.00 mA if output
is set to mA (default =
0.00) (* 1000)
Vista de página 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 31 32

Comentários a estes Manuais

Sem comentários