Watlow Series SD6 PID with DeviceNet 23
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
122 Get Integral Term UINT View the active integral term
for PID diagnostics.
0.000 to 1.000
(this value multiplied by
100 equals the percent
power)
123 Get Derivative Term UINT View the active derivative term
for PID diagnostics.
0.000 to 1.000
(this value multiplied by
100 equals the percent
power)
124 Get/Set Alarm 1 High Temperature DINT Set the high alarm set point. 0 to 9999 (* 1000) if
Sensor Type is set to
Thermocouple or RTD
(default = 999)
125 Get/Set Alarm 1 High Process DINT Set the high alarm set point. -1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 1500)
126 Get/Set Alarm 1 Low Temperature DINT Set the low alarm set point. -1999 to 0 (* 1000) if
Sensor Type is set to
Thermocouple or RTD
(default = -999)
127 Get/Set Alarm 1 Low Process DINT Set the low alarm set point. -1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 32)
128 Get/Set Alarm 2 High Temperature DINT Set the high alarm set point. 0 to 9999 (* 1000) if
Sensor Type is set to
Thermocouple or RTD
(default = 999)
129 Get/Set Alarm 2 High Process DINT Set the high alarm set point. -1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 1500)