Watlow EZ-ZONE RM-Scanner-Modul Manual do Utilizador Página 26

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 140
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 25
Watlow EZ-ZONE
®
RMS Module 23 Chapter 2 Install and Wire
Warning: ç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12 AWG)
single-wire termination or two 1.31
mm
2
(16 AWG)
• 0.8 Nm (7.0 in-lb.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the controller,
do not connect wires to unused ter-
minals.
Note:
Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs
to prevent ground loops.
Warning: ç
Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2.
Warning: ç
Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.
Scanner Module Wiring (RMSx-xxxx-xxxx)
Low Power
RMS- ALL Model Numbers
98
99
S
l
o
t
C
power
20.4 to 30.8 V Å (ac) / Î (dc)
47 to 63 Hz
14VA (ac), 7 VA (dc) maximum consumption
Controller module power consumption, 7 Watts maxi-
mum
31 Watts maximum power available for P/S part
#:0847-0299-0000
60 Watts maximum power available for P/S part
#:0847-0300-0000
91 Watts maximum power available for P/S part
#:0847-0301-0000
Class 2 or SELV power source required to meet UL
compliance standards
Communications
RMS Part # Digit 10 is A
CF
CD
CE
CZ
CX
CY
S
l
o
t
C
Standard Bus
Common
T- / R-
Inter-module Bus
Common
-
+
T+ / R+
CF, CD, CE - Standard Bus EIA485 Communications
CZ, CX, CY - Inter-module Bus EIA485 Communica-
tions
Do not route network wires with power wires. Connect
network wires in daisy-chain fashion when connecting
multiple devices in a network
Communications
RMS Part # Digit 10 is 1
CC
CA
CB
CZ
CX
CY
S
l
o
t
C
T+ / R+
Modbus
Common
T- / R-
Inter-module Bus
Common
+
-
CC, CA, CB - Modbus and Standard Bus EIA-485
Communications (selectable via push button under
zone address)
CZ, CX, CY - Inter-module Bus EIA-485 Communica-
tions
Do not route network wires with power wires. Con-
nect network wires in daisy-chain fashion when con-
necting multiple devices in a network
Inputs 1 through 16 Thermocouple
RMS Part # Digits 5, 6, 7, 8
-
+
-
+
-
+
-
+
Thermocouple
S_
R_
S_
R_
S_
R_
S_
R_
Slot A, B, D, E
2K Ω maximum source resistance
>20 MΩ input impedance
3 microampere open-sensor detection
Thermocouples are polarity sensitive. The negative
lead (usually red) must be connected to S terminal
To reduce errors, the extension wire for thermocouples
must be of the same alloy as the thermocouple.
Input 1 - 4 (top to bottom): RMSx-(R)xxx-xxxx
Input 5 - 8 (top to bottom): RMSx-x(R)xx-xxxx
Input 9 - 12 (top to bottom): RMSx-xx(R)x-xxxx
Input 13 - 16 (top to bottom): RMSx-xxx(R)-xxxx
Vista de página 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 139 140

Comentários a estes Manuais