Watlow EZ-ZONE
®
RMS Module 35 Chapter 3 Operations Page
RM Scanner Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[``Ai]
[oPEr]
Analog Input Menu
[``Ain]
[ Ain]
Analog Input (1 to 16)
Input Value
View the process value.
Note:
Ensure that the Error
Status (below) indicates
no error (61) when read-
ing this value using a
field bus protocol. If an
error exists, the last
known value prior to the
error occurring will be
returned.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 380
[offset 90]
0x68 (104)
1 to 0x10
(16)
1
0 4001 float
R
No Dis-
play
Analog Input (1 to 16)
Filtered Process Value
View the process value
when filtering is turned on.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 422
[offset 90]
0x68 (104)
1 to 0x10
(16)
0x16 (22)
- - - - 4022 float
R
[`i;Er]
[ i.Er]
Analog Input (1 to 16)
Input Error
View the cause of the most
recent error.
[nonE] None (61)
[OPEn] Open (65)
[Shrt] Shorted (127)
[`E;M] Measurement Error
(140)
[E;CAL] Bad Calibration
Data (139)
[Er;Ab] Ambient Error (9)
[E;;Rtd] RTD Error (141)
[FAiL] Fail (32)
[Nsrc] Not Sourced (246)
None 382
[offset 90]
0x68 (104)
1 to 0x10
(16)
2
1 4002 uint
R
[`i;Ca]
[ i.CA]
Analog Input (1 to 16)
Calibration Offset
Offset the input reading to
compensate for lead wire
resistance or other factors
that cause the input read-
ing to vary from the actual
process value.
-1,999.000 to 9,999.000°F
or units
-1,110.555 to 5,555.000°C
0.0 402
[offset 90]
0x68 (104)
1 to 0x10
(16)
0xC (12)
2 4012 float
RWES
No Dis-
play
Analog Input (1 to 16)
Clear Latched Input Er-
ror
Clear latched input when
input error condition no
longer exists.
Clear Latch (1221) - - - - 436
[offset 90]
0x68 (104)
1 to 0x10
(16)
0x1D (29)
- - - - 4029 uint
W
[``Pu]
[oPEr]
Process Value Menu
[`Su;A]
[ Sv.A]
Process Value (1 to 16)
Source Value A
View the value of Source A.
-1,999.000 to 9,999.000°F
or units
-1,110.556 to 5,555.000°C
- - - - 5210
[offset 70]
0x7E (126)
1 to 0x10
(16)
0x10 (16)
- - - - 26016 float
R
[`Su;b]
[ Sv.b]
Process Value (1 to 16)
Source Value B
View the value of Source B.
-1,999.000 to 9,999.000°F
or units
-1,110.556 to 5,555.000°C
- - - - 5212
[offset 70]
0x7E (126)
1 to 0x10
(16)
0x11 (17)
- - - - 26017 float
R
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set