RME Module 21 Chapter 2 Install and Wire
Warning: ç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.
Note:
Maximum wire size termination
and torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination
or two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 in-lb.) torque
Note:
Adjacent terminals may be la-
beled differently, depending on
the model
number.
Note:
To prevent damage to the con-
troller, do not connect wires to
unused terminals.
Note:
Maintain electrical isolation
between digital input-outputs,
switched dc/open collector out-
puts and process outputs
to
prevent ground loops.
Note:
If the last two digits of the part
number are "12", this equip-
ment is suitable for use in
CLASS I, DIVISION 2, Groups
A, B, C and D or Non-Hazard-
ous locations
only. Temperature
Code T4
Warning: ç
Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2.
Warning: ç
Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.
Quencharc Note:
Switching pilot duty inductive loads
(relay coils, solenoids, etc.) with the
mechanical relay, Solid-State relay or
open collector output options requires
use of an R.C. suppressor.
Digital Inputs 1 to 24
RME Part # Digit 5, 6, 7, 8 is C
Common
DC Input
B_
D_
D_
D_
D_
D_
D_
Z_
Slot A, B, D, E
Int
ernal Supply
DC Input
DC Input
DC Input
DC Input
DC Input
Digital Input Event Condi-
tions
• Dry Contact
- Input inactive when >
100KΩ
- Input active when <
50Ω
• Voltage
- Input inactive when <
2V
- Input active when > 3V
• Six user configurable
Digital Inputs per slot
Voltage Input
common
Vdc
B_
D_
Dry Contact
24 Vdc
Z_
D_
Digital Outputs 1 to 24
RME Part # Digit 5, 6, 7, 8 is C
Common
Collector out
Collector out
B_
D_
D_
D_
D_
D_
D_
Z_
Slot A, B, D, E
Collector out
Collector out
Collector out
Collector out
Internal Suppl
y
• Maximum switched
voltage is 32VÎ
(dc)
Internal supply
provides a constant
power output of
750mW
Maximum output
sink current per
output is 1.5A (ex-
ternal class 2 or
*SELV supply re-
quired)
Total sink current
for all outputs not
to exceed 8A
• Do not connect out-
puts in parallel
*Safety Extra Low
Voltage
Commo
n
Internal
Supply
Vdc
D_
B_
D_
D_
D_
D_
Z_
D_
• Six user configurable Digital Out-
puts per slot