Watlow EZ-ZONE
®
RME Module 38 Chapter 3 Operations Page
RME Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
No Dis-
play
Special Output Function
(1 to 4)
Error 2
Read reported cause for
output error.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - 6644
[offset 80]
0x87
(135)
1 to 4
0x0D (13)
- - - - 35013 uint
R
[`o;u3]
[ o.v3]
Special Output Function
(1 to 4)
Output Value 3
View the value of this
function's Output 3.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 6646
[off 80]
0x87
(135)
1 to 4
0xE (14)
- - - - 35014 float
R
No Dis-
play
Special Output Function
(1 to 4)
Error 3
Read reported cause for
output error.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - 6648
[offset 80]
0x87
(135)
1 to 4
0x0F (15)
- - - - 35015 uint
R
[`o;u4]
[ o.v4]
Special Output Function
(1 to 4)
Output Value 4
View the value of this
function's Output 4.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 6650
[off 80]
0x87
(135)
1 to 4
0x10 (16)
- - - - 35016 float
R
No Dis-
play
Special Output Function
(1 to 4)
Error 4
Read reported cause for
output error.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - 6652
[offset 80]
0x87
(135)
1 to 4
0x11 (17)
- - - - 35017 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EE-
PROM
S: User
Set